直流(liu)電(dian)(dian)(dian)流(liu)表外附(fu)分(fen)流(liu)器(qi)(qi) 分(fen)流(liu)器(qi)(qi)是(shi)測量直流(liu)電(dian)(dian)(dian)流(liu)用(yong)的,分(fen)流(liu)器(qi)(qi)是(shi)分(fen)流(liu)器(qi)(qi)是(shi)測量直流(liu)電(dian)(dian)(dian)流(liu)用(yong)的,根(gen)據(ju)直流(liu)電(dian)(dian)(dian)流(liu)通過電(dian)(dian)(dian)阻(zu)時(shi)在電(dian)(dian)(dian)阻(zu)兩(liang)端產(chan)生電(dian)(dian)(dian)壓的原理(li)制成(cheng),分(fen)流(liu)器(qi)(qi)是(shi)指測量直流(liu)電(dian)(dian)(dian)流(liu)用(yong)的,根(gen)據(ju)直流(liu)電(dian)(dian)(dian)流(liu)通過電(dian)(dian)(dian)阻(zu)時(shi)在電(dian)(dian)(dian)阻(zu)兩(liang)端產(chan)生電(dian)(dian)(dian)壓的原理(li)制成(cheng)上(shang)海康(kang)登電(dian)(dian)(dian)氣科技有限(xian)公司可(ke)以定制分(fen)流(liu)器(qi)(qi)提供方案。
型號:
瀏覽量:1562
更新時間:2023-11-07
在線留言品牌 | 其他品牌 | 產地類別 | 國產 |
---|---|---|---|
應用領域 | 環保,化工,地礦,能源,電子 |
直流電流表外附分流器
直流電流表外附分流器的額定電壓(ya)降(jiang)為75mV,供在直流電路中(zhong),配合75mV量限(xian)的磁(ci)點(dian)系毫伏(fu)表(biao),康(kang)登智(zhi)能電流表(biao),安(an)培小時(shi)計(ji),庫侖計(ji)等(deng)作測量大電流之用(yong)。
此分(fen)流(liu)器工作與周圍空氣溫(wen)度自(zi)+20度到+50度及相對溫度小于85%,且空(kong)氣(qi)中(zhong)不含有腐蝕性雜質的環境中(zhong)。
本分流器適宜(yi)于固(gu)定的安(an)裝在饋流母線(xian)排上。接(jie)頭與母線(xian)間的接(jie)觸面積應清潔(jie)平(ping)整(zheng)。分流器的縱軸(zhou)水(shui)平(ping)安(an)置(zhi),按(an)頭的便(bian)面位于垂直位置(zhi)。電(dian)位端子接(jie)75mV 毫伏表 (例如YK-31智能電流(liu)表(biao)),此(ci)接線是定(ding)制的,應符合該(gai)毫伏(fu)表(biao)的要求。
主要技術參數
1、準確度等級:2~4000A;0.5級:5000~30000A;1級。
2、環境條件:-40~+60℃,相對溫度≤95%(35℃)。
3、超載性能:額定電流120%,2小時。
4、電壓降:50mV60mV70mV100mV
5、負載下發熱:溫升變化趨于穩定后,額定電流50A以下不超過80℃;額定電流50A以上不超過120℃。
分流器接線示意圖
注意事項
一、分流器一次回路(lu)的電纜(或銅排(pai))與分流器連接處不允許有人為(wei)的接觸(chu)電阻,二次電壓的取(qu)(qu)樣點不能從非取(qu)(qu)樣點取(qu)(qu)樣。
二、實際使用的電(dian)流(長時間)建議不超過額定電(dian)流的
80%。
5~50A分流器
50A分(fen)流(liu)器
75A~100A分流器
150A~200A分流器(qi)
300A分(fen)流器
400A分(fen)流器
500A分流器
600A分(fen)流器
750A分流器
1000A分流器(qi)
2000A分流器
3000A分流器(qi)
20000A分流器